Equipment
Composition
- GENERAL
- (Brick) An equipment can only be comprised of other equipment ✅
- (Brick) Equipment can be part of another Equipment(s) or Collection(s). ✅
- An Equipment should only be part of at most ONE equipment ❌
- TARGETED
- VAV
- A VAV must have a Damper ✅
- Single Duct with Reheat
- Must also have a Heating Coil ✅
- Dual Duct
- Must also have an additional Damper ✅
- Fan Powered
- Must also have a Fan ✅
- Bypass
- Must have a Bypass Damper instead of just a Damper ✅
- VFD
- Damper
- Fan
- VAV
Relationships
- GENERAL
- (Brick) An equipment can
hasLocation
only at a Location ✅ - (Brick) An equipment can
feed
only Equipment(s) or Locations(s) ✅
- (Brick) An equipment can
- TARGETED
- Meters
- Electrical Meters
- (
A meter
meters
an Equipment(s) OR A meterhasSubMeter
of another meter ) ✅ - [DISABLED] (
A meter
isSubMeterOf
another meter OR A meterisPartOf
an InvoiceStream ) ✅ - A meter
meters
an Equipments(s) excl. Meters ❌ - A meter
hasSubMeter
of the same category (substance?) as itself ❌
- (
A meter
- Electrical Meters
- VFD
- A VFD must be directly
partOf
a Pump or Fan ✅
- A VFD must be directly
- Meters
Points
- GENERAL
- (Brick) An equipment can
hasPoint
of Point(s) ✅
- (Brick) An equipment can
Locations
Composition
- GENERAL
- (Brick) A location can only be comprised of other locations. ✅
- A location should only be part of at most ONE location (excl. Zones) ✅
Points
- GENERAL
- (Brick) A location cannot be the sole parent of a point [validated via Point rules] ❌